TRE series circuit breakers and auxiliaries comply with the following international standard:
IEC/EN 60947-1: Low-voltage switchgear and controlgear-Part 1: General rules
IEC/EN 60947-2: Low-voltage switchgear and controlgear-Part 2: Circuit breakers
TRE series ELCB(Standard use environment for TRE series ELCB)
1. Ambient temperature: Within the range of -5ºC--+40ºC(However, the average for the duration of 24 hours must not exceed 35ºC);
2. Altitude: 2000m or less
3. Installation class: III
4. The magnetic field near the instalation site should not be more than five times the earth magnetic field in any direction.
5. Pollution: II
Classification:
According to the poles: 2-poles, 3-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)
According to the trip action time: Fix type, Adjustable type(0.1s/0.3s/0.5s or 0.45s/1.0s/2.0s)
According to the rated residual current: Fix type, Adjustable type(30mA/100mA/300mA/500mA)
| Frame size | TREF1 (63A) | ||||
| Breaking capacity code | S | H | |||
| Type and pole | 2P | 3P | 2P | 3P | |
| TREF1-S2 | TREF1-S3 | TREF1-H2 | TREF1-H3 | ||
| Protective function | Overload & Short-circuit & Ground fault | ||||
| Rated current ,In (A) | 15A, 20A, 30A, 40A, 50A, 63A | ||||
| Rated residual current | Operating ,IΔn (mA) | 30mA, 50mA,100mA,200mA,300mA,500mA | |||
| Non-operating ,IΔno (mA) | 15mA,25mA,50mA,100mA,150mA,250mA | ||||
| Adjustable part | Rated current setting(0.8In~1.0In) | √ | √ | ||
| Lockup device for operating handle | - | √ | - | √ | |
| Residual current setting, IΔn | 30mA / 100mA / 300mA / 500mA | ||||
| Trip action time setting | 0.1s / 0.3s / 0.5s | ||||
| Rated operational voltage ,Ue (V) ,AC 50/60 Hz | 240V/415V | ||||
| Rated insulation voltage ,Ui (V) | 1000V | ||||
| Rated impulse withstand voltage ,Uimp (KV) | 8kV | ||||
| Residual current off-time at IΔn ,Sec (s) | 0.1s | ||||
| Standard | Conformity with IEC / EN 60947-2 | ||||
| Rated frequency (Hz) | 50/60 Hz | ||||
| Rated short-circuit breaking capacity ,Icu (KA) | |||||
| AC | 240V | 14kA | 25kA | ||
| 415V | 5kA | 7.5kA | |||
| Ics=%*Icu | 100% | ||||
| Mechanical life (circle) | 8500 | ||||
| Electrical life (circle) | 1500 | ||||
| Dimension Length*Width*Height(mm) | 2-pole | 100mm*50mm*60mm | |||
| 3-pole | 100mm*75mm*60mm | ||||
| 4-pole | - | ||||
Built-in accessory: